Conduit Fill Calculator

By Andrew ·

Quick answer

Conduit fill is the total cross-section of the wires as a share of the conduit's inside area. NEC Chapter 9, Table 1 allows 53% for one wire, 31% for two and 40% for three or more. In 1/2" EMT (0.304 in² inside), 40% is 0.1216 in²; a 12 AWG THHN takes 0.0133 in², so 9 fit, filling 39.4%.

Calculator

Results
Fill
39.4%
NEC limit for this many wires
40%
Most wires of this size that fit
9
Within the limit?
Yes

From NEC Chapter 9, Tables 1, 4 and 5, with every wire THHN/THWN-2 and the same size. A count that Note 7 rounds up to is allowed, even a little over 40%. Your inspector and local code edition have the final word.

Three tables do all the work

Every conduit fill check uses three tables in Chapter 9 of the NEC. Table 4 gives the inside area of each conduit type and trade size. Table 5 gives the area of each wire, insulation included. Table 1 says how much of the conduit the wires may fill.

fill % = total wire area ÷ conduit area × 100
Both areas in square inches. Compare the result with the Table 1 limit for that many wires.
Chapter 9, Table 1: the most a conduit may be filled
Wires in the conduitMaximum fill
153%
231%
3 or more40%

The inside area depends on the conduit type as well as the trade size, because the walls are different thicknesses. 1/2" EMT, rigid and PVC are three different numbers in Table 4, so pick the right type before you trust the answer.

Worked example: 12 AWG THHN in 1/2" EMT

How many 12 AWG THHN fit in 1/2" EMT
Inside area of 1/2" EMT (Table 4)
0.304 in²
Area of 12 AWG THHN (Table 5)
0.0133 in²
Limit for three or more wires (Table 1)
40%
Room for wire
0.304 in² × 0.40 = 0.1216 in²
Wires
0.1216 ÷ 0.0133 = 9.14, so 9
Fill with that many
9 × 0.0133 ÷ 0.304 = 39.4%

The decimal is dropped because of Note 7 to the Chapter 9 tables: when the wires are all the same size, round the count up to the next whole number only when the decimal is 0.8 or more. 8 AWG THHN in 3/4" EMT works out to 5.83, so 6 are allowed, even though 6 of them fill 41.2%.

Mixed sizes, grounds and nipples

  1. Look up each wire in Table 5. THHN, THWN and THWN-2 share one row.
  2. Multiply each area by how many wires of that size there are, and add them up.
  3. Count every wire, the ground included, to pick the limit: 40% for three or more.
  4. Compare the total with that share of the conduit’s Table 4 area.
Three 10 AWG and four 12 AWG THHN in 1/2" EMT
10 AWG
3 × 0.0211 = 0.0633 in²
12 AWG
4 × 0.0133 = 0.0532 in²
Total wire area
0.1165 in²
40% of 1/2" EMT
0.1216 in²
Fill
38.3%, within the limit
  • Grounds count. Note 3 includes equipment grounding and bonding conductors in the fill. Use the Table 5 area for an insulated one and the Table 8 area for a bare one.
  • Short nipples get 60%. Under Note 4, a nipple no longer than 24" between boxes, cabinets and similar enclosures may be filled to 60%, and the 310.15(C)(1) adjustment factors don’t apply to it.
  • Insulation changes the answer. The numbers here are for THHN/THWN-2. XHHW-2, common on feeders, is thicker than THHN in the small sizes, so fewer fit; use its own row in Table 5.
  • Annex C has it worked out. Its tables list the most wires of one size and insulation for each conduit type and trade size, calculated from Tables 1, 4 and 5 with Note 7. They only cover wires that are all the same size.

How many THHN wires fit

Most THHN/THWN-2 wires of one size in EMT (Chapter 9 with Note 7, as in Annex C)
EMT size14 AWG12 AWG10 AWG8 AWG6 AWG
1/2"129531
3/4"22161064
1"35261697
1-1/4"6145281612
1-1/2"8461382216
2"138101633626
Most 12 AWG THHN/THWN-2 wires, by conduit type
Trade sizeEMTRigidIMCPVC 40PVC 80
1/2"991086
3/4"1616171512
1"2626292520
1-1/4"4546494337
1-1/2"6162675951
2"1011021099986

From 1/2" to 2", IMC has the largest inside of the five and PVC Schedule 80, with the thickest wall, the smallest. The ground counts toward every number in these tables.

Fill is only one of the checks

Fill only says the wires fit. When a conduit carries more than three current-carrying conductors, their ampacity has to be adjusted under 310.15(C)(1) (the 2020 and 2023 numbering): to 80% for 4 to 6, 70% for 7 to 9 and 50% for 10 to 20. Up to 9 wires of 12 AWG fit in 1/2" EMT, but if 7 or more of them carry current, each is good for only 70% of its ampacity.

An informational note to Table 1 also warns about jamming: when three wires are pulled in, they can jam if the conduit’s inside diameter is 2.8 to 3.2 times the wire’s outside diameter. It is mostly a concern with three larger single conductors, and the fill percentage won’t show it.

  • Using EMT areas for rigid or PVC, which have different insides.
  • Leaving the ground wire out of the count.
  • Using the THHN area for XHHW, TW or another insulation.
  • Rounding a count such as 9.5 up to 10. Only a decimal of 0.8 or more rounds up.
  • Treating 40% as a target. A full conduit with several bends is a hard pull, and going up a size makes it easier.

Get the marks for your bender

BendMate works this out from your bender’s radius and deduct, flags a bend that won’t work, and shows you every mark.

Free for offsets, saddles, 90s and kicks with a hand bender. No signup.

Common questions

How many 12 AWG wires can go in 1/2" EMT?

9 THHN/THWN-2, by Chapter 9 and Annex C. In 3/4" EMT it is 16 and in 1" EMT 26, and the ground wire counts toward each number.

How many 10 AWG THHN fit in 3/4" EMT?

10. In 1/2" EMT it is 5, and in 3/4" PVC Schedule 40 it is 9, because PVC has a smaller inside than EMT.

What is the 40% conduit fill rule?

NEC Chapter 9, Table 1 lets three or more wires fill up to 40% of a conduit’s inside area. One wire may fill 53% and two wires 31%, and a nipple 24" or shorter may be filled to 60%.

Does the ground wire count in conduit fill?

Yes. Note 3 to the Chapter 9 tables includes equipment grounding and bonding conductors, using the Table 5 area for an insulated one and the Table 8 area for a bare one.

When can you round up in conduit fill?

Only when every wire is the same size and the count works out to a decimal of 0.8 or more (Note 7). That is why 3/4" EMT takes 6 wires of 8 AWG THHN, where the math gives 5.83.