Skip to content
BendMateGet BendMate

Voltage Drop Calculator

By Andrew ·

Quick answer

Single-phase voltage drop is 2 × K × I × L ÷ CM: K is 12.9 for copper or 21.2 for aluminum, I the current, L the one-way length in feet and CM the wire's circular mils. Three phase uses 1.732 in place of 2. A 20 A load 100 ft away on 12 AWG copper at 120 V loses 7.9 V (6.6%); 8 AWG keeps it within 3%.

Calculator

Results
Voltage drop
7.9 V
Drop as a percent
6.6%
Voltage at the load
112.1 V
Smallest wire for a 3% drop
8 AWG

The K-factor formula, with K = 12.9 for copper and 21.2 for aluminum and the wire areas in NEC Chapter 9, Table 8. It ignores reactance, which matters on large wire and long runs.

The K-factor formula

VD = 2 × K × I × L ÷ CM
Single phase. The 2 covers the wire out and the wire back, so L is the one-way length.
VD = 1.732 × K × I × L ÷ CM
Three phase, line to line. 1.732 is √3.
  • K is the resistance in ohms of a wire one circular mil in area and one foot long: about 12.9 for copper and 21.2 for aluminum, from the resistances in Chapter 9, Table 8 at 75 °C.
  • I is the load current in amps.
  • L is the one-way length from the source to the load in feet, measured along the route the wire takes.
  • CM is the wire’s area in circular mils, from Chapter 9, Table 8.
Chapter 9, Table 8: area in circular mils
WireCircular mils
14 AWG4,110
12 AWG6,530
10 AWG10,380
8 AWG16,510
6 AWG26,240
4 AWG41,740
3 AWG52,620
2 AWG66,360
1 AWG83,690
1/0 AWG105,600
2/0 AWG133,100
3/0 AWG167,800
4/0 AWG211,600

A kcmil size is its own number of thousands: 250 kcmil is 250,000 circular mils. Divide the drop by the supply voltage for the percent.

Worked example: 20 A, 100 ft away

120 V, 20 A, 100 ft one way, 12 AWG copper
System
Single phase, 120 V
Load current
20 A
One-way length
100 ft
Wire
12 AWG copper, 6,530 CM
Voltage drop
2 × 12.9 × 20 × 100 ÷ 6,530 = 7.9 V
Drop as a percent
7.9 V ÷ 120 V = 6.6%
Voltage at the load
112.1 V
Smallest wire for 3%
8 AWG

To find the wire for a target drop, turn the formula around and solve for the circular mils.

CM = 2 × K × I × L ÷ allowed volts
3% of 120 V is 3.6 V, so CM = 2 × 12.9 × 20 × 100 ÷ 3.6 = 14,333. 10 AWG (10,380 CM) is too small; 8 AWG (16,510 CM) is the first size above it.

Checked the other way: 10 AWG drops 4.97 V (4.1%) on this circuit and 8 AWG drops 3.13 V (2.6%).

Three phase, and copper against aluminum

208 V three phase, 40 A, 150 ft, 8 AWG copper
System
Three phase, 208 V
Load current
40 A
One-way length
150 ft
Wire
8 AWG copper, 16,510 CM
Voltage drop
1.732 × 12.9 × 40 × 150 ÷ 16,510 = 8.12 V
Drop as a percent
8.12 V ÷ 208 V = 3.9%
Voltage at the load
199.88 V
Smallest wire for 3%
6 AWG, which drops 5.11 V (2.5%)

On three phase the percent is of the line-to-line voltage, 208 V here.

A 240 V, 60 A load 200 ft away, in copper or aluminum
System
Single phase, 240 V
Load current
60 A
One-way length
200 ft
6 AWG copper
11.8 V, 4.9%
4 AWG aluminum
12.19 V, 5.1%
Smallest copper for 3%
3 AWG
Smallest aluminum for 3%
1 AWG

Aluminum’s K is about 64% higher than copper’s, so for the same drop it takes about two sizes bigger.

3% and 5% are recommendations

The figures everyone quotes come from informational notes in the NEC, in 210.19(A) for branch circuits and 215.2(A) for feeders. They suggest no more than 3% on a branch circuit or a feeder, and no more than 5% for the feeder and branch circuit together, for reasonable efficiency of operation.

Informational notes are not enforceable, so for ordinary circuits the NEC sets no voltage drop limit. Some specific articles, engineers’ specifications and local rules do, and your AHJ has the final say.

Smallest copper wire for a 3% drop at 120 V, single phase
One-way length15 A load20 A load
50 ft12 AWG10 AWG
75 ft10 AWG8 AWG
100 ft8 AWG8 AWG
150 ft8 AWG6 AWG
200 ft6 AWG4 AWG

Where the simple formula falls short

  • It uses DC resistance and ignores reactance. On large conductors, long feeders and loads with a low power factor, such as motors, the real drop can be noticeably different, and an AC calculation that includes reactance is more accurate.
  • K is for wire at 75 °C. Lightly loaded wire runs cooler and drops a little less, so the answer leans conservative.
  • L is the one-way length. Don’t double it: the 2, or the 1.732, already accounts for the return path.
  • Use the current the load actually draws. Using the breaker rating instead gives a conservative answer.
  • A motor draws several times its running current while it starts, so the drop at starting is much bigger than the steady figure.

Get the marks for your bender

BendMate works this out from your bender’s radius and deduct, flags a bend that won’t work, and shows you every mark.

Free for offsets, saddles, 90s and kicks with a hand bender. No signup.

Common questions

What is the maximum voltage drop allowed by the NEC?

For ordinary branch circuits and feeders there is no enforceable maximum. Informational notes in 210.19(A) and 215.2(A) recommend 3% for a branch circuit or feeder and 5% for both together, and some specific articles, job specifications and local rules do set limits.

What size wire do I need for 20 amps at 100 feet?

For a 3% drop at 120 V on copper, 8 AWG, which drops 3.13 V. At 240 V, 10 AWG is enough. It can never be smaller than the circuit's ampacity requires, which is 12 AWG copper for an ordinary 20 A circuit.

How do you calculate voltage drop?

Multiply 2 × K × amps × one-way feet and divide by the wire's circular mils, with K = 12.9 for copper or 21.2 for aluminum. For three phase use 1.732 instead of 2, and divide the drop by the supply voltage for the percent.

Is voltage drop calculated with the one-way or round-trip length?

Enter the one-way length from the source to the load. The 2 in the single-phase formula, or the 1.732 for three phase, already accounts for the return path.

What is K in the voltage drop formula?

K is the resistance of a conductor one circular mil in area and one foot long: about 12.9 ohms for copper and 21.2 ohms for aluminum at 75 °C, worked out from the resistances in Chapter 9, Table 8.